LRS-100N2-24
Request a Backorder
Submit your request and we will confirm lead time.
Submit your request and we will confirm lead time.
AC input voltage range
85 ~ 264VAC 120 ~ 373VDC (Withstand 300VAC surge for 5sec. Without damage)
AC inrush current (max.)
COLD START 55A/230VAC
Overload protection
Output power >105% rated for more than 5 seconds then shut down o/p voltage, re-power on to recover
Output power >200% rated, hiccup mode, recovers automatically after fault condition is removed
Over-voltage protection
| 13.8 ~ 16.2V | 28.8 ~ 33.6V | 41.4 ~ 48.6V | 55.2 ~ 64.8V |
Shut down and latch off o/p voltage, and re-power on to recover
Withstand voltage
I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:1.25KVAC
Working temperature
-30 ~ +70℃ (Refer to "Derating Curve")
Safety standards
UL 62368-1, TUV BS EN/EN62368-1, BS EN/EN61558-1/-2-16,GB 4943.1,BSMI CNS15598-1, EAC TP TC 004,S/NZS62368.1(by CB), BIS IS13252(Part1): 2010/IEC 60950-1: 2005(except for 48V) approved Designed refer to AS/NZS 61558.1/2.16, AS/NZS 62368.1
Dimension (LxWxH)
129x97x30mm
Your payment information is securely processed through encrypted and PCI-compliant payment systems. We do not store, collect, or have access to your credit card details. All transactions are handled by trusted payment providers to ensure your personal and financial information remains safe and protected at all times.